01 · ATTENTION
Water damage often begins before water reaches the building.
Part 3.3 is not a collection of isolated dimensions. It is a coordinated defence that moves surface water, subsurface water and stormwater away from the building.
01 · ATTENTION
Part 3.3 is not a collection of isolated dimensions. It is a coordinated defence that moves surface water, subsurface water and stormwater away from the building.
02 · INTEREST
The drainage strategy becomes easier to review when it is separated into the three pathways identified by Part 3.3.
03 · DESIRE
A compliant number does not rescue a site where water is trapped against the building.
Always confirm which condition applies. Do not select the smallest number by default.
04 · APPLICATION
Where subsurface water needs to be diverted, the drain requires a uniform fall of at least 1:300, a maintainable outlet and a considered relationship with the soil and footings.
05 · SITE CHECK
The system must satisfy the appropriate authority and prevent heavy-rain overflow from returning to the building.
| Location above 90 mm Class 6 UPVC | Minimum cover |
|---|---|
| Soil | 100 mm |
| Paved or concrete area | 50 mm |
| Light vehicle area, reinforced concrete | 75 mm |
| Light vehicle area, paved | 100 mm |
Cover is measured from the top of the pipe to finished ground level, or to the underside of paving or concrete.
06 · KNOWLEDGE CHECK
Answer all five questions. You need four correct answers to complete the learning.